Fire-Lite Alarms MS-9600LS Manual page 190

Addressable fire alarm control panel
Table of Contents

Advertisement

NFPA Standard-Specific Requirements
NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1.
3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2.
Cut JP6 on the FACP main circuit board to supervise placement of 4XTMF module and circuit.
3.
Cut JP5 on the FACP main circuit board to enable FACP Supervisory relay.
4.
Refer to "4XTMF Transmitter Module Installation" on page 55 for detailed information.
Polarities shown in alarm condition
4XTMF
Figure C.3 Municipal Box Connected to 4XTMF Transmitter Module
190
Municipal Box Circuit
Local Energy Municipal Box
Nonpower-limited
-
+
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010