Step
HP BladeSystem c7000 Enclosure Insight Display action and verification
Action
Step 2
Check the Insight Display to be sure that no firmware updates are in progress.
Verification
Do one of the following:
If the enclosure is performing a firmware update, then wait until the firmware update is
complete. When the update is complete, continue to the next step.
If the enclosure is not performing a firmware update, then continue to the next step.
Action
Step 3
If one Onboard Administrator is installed in the enclosure, then continue to step 4.
If two Onboard Administrators are installed in the enclosure, then perform the following
substeps:
1
Locate the standby Onboard Administrator. The active LED on the standby Onboard
Administrator is off.
2
Remove the standby Onboard Administrator.
Action
Step 4
Reseat the active Onboard Administrator.
Verification
Wait for up to 2 minutes, and then check the Insight Display.
If the issue still exists, continue to the next step.
If the Insight Display illuminates and the Insight Display buttons operate properly, then
install the standby Onboard Administrator in the original bay. The repair is complete.
Action
Step 5
Test OA bay Y:
1
Remove the Onboard Administrator (suspect OA #X) from OA bay X.
2
Install the Onboard Administrator (suspect OA #X) in OA bay Y.
Verification
Wait for up to 2 minutes, and then check the Insight Display.
If the issue still exists, continue to the next step.
If the Insight Display illuminates and the Insight Display buttons operate properly, then
test the OA tray connection. Continue to step 9.
Action
Step 6
Test the Onboard Administrator:
1
Remove OA #X.
2
Install the OA #Y, if present, or an operational Onboard Administrator into OA bay 1.
Verification
Wait for up to 2 minutes, and then check the Insight Display.
If the issue still exists, then test the OA tray connection. Continue to step 9.
If the Insight Display illuminates and the Insight Display buttons operate properly, then
OA #X failed.
If OA #X has failed, do one of the following:
If replacing OA #X with a service spare part, then continue to the next step.
If replacing OA #X with OA #Y, then continue to step 8.
Action
Step 7
Obtain the OA1 IP settings from the enclosure administrator.
HP BladeSystem Insight Display troubleshooting 20