Xantrex_PRO1800.book Page 3 Tuesday, April 24, 2007 11:33 AM
Table 5-1 Fault Codes
Fault
Status
Code
LED
Description
E01
Yellow
Under-voltage
warning
E02
Red
Under-voltage
shutdown
E03
Red
Over-voltage
shutdown
E04
Yellow
Overload shutdown
warning
E05
Red
Overload shutdown
Short circuit
E06
Not used
E07
Yellow
Over-temperature
shutdown warning
E08
Red
Over-temperature
shutdown
975-0263-01-01
Solution
Check the connections and cable to see if the battery is fully
charged. Recharge the battery if it is low.
Reduce the load.
Disconnect the load and recharge the battery.
Make sure the XM 1800 is connected to a 12 V battery.
Make sure the load does not exceed the XM 1800's output
rating. Reduce the load if necessary.
Reduce or disconnect the load. Make sure the load does not
exceed the XM 1800's output rating.
Check connection to the load.
Allow the unit to cool off. Reduce the load if continuous
operation is required.
Improve ventilation. Make sure the inverter's ventilation
openings are not obstructed.
Reduce the ambient temperature.
Allow the unit to cool off.
Improve ventilation. Make sure the inverter's ventilation
openings are not obstructed.
In order to reset the unit after an error has occurred, you have to
Important:
remove shorepower (i.e., AC input), turn the unit off, then turn back on again.
Understanding Fault Codes