Xantrex_PRO1800.book Page 19 Tuesday, April 24, 2007 11:33 AM
11. Insert the Line and Neutral wires into the corresponding terminals.
12. Tighten the wire attachment screws to a torque of 1.3–1.8 lbf-ft (1.76–
13. Secure the strain-relief clamp.
14. Attach the wiring compartment cover.
15. Connect the outgoing AC wires to the AC load panel.
975-0263-01-01
CAUTION: Reverse polarity
Improper connections (connecting a line conductor to a neutral conductor, for
example) will cause the XM 1800 to malfunction and may permanently damage
the inverter. Damage caused by a reverse polarity connection is not covered by
your warranty.
2.44 Nm). Leave some wiring slack inside the wiring compartment.
Ensure you have maintained correct polarity and that there are no loose
strands of wire.
AC Wiring
3–19