Switching Operation Source To Communication Option Card; Jog Frequency With Direction Commands (Fjog/Rjog) - Omron VARISPEED F7 User Manual

Vector control frequency inverter
Hide thumbs Also See for VARISPEED F7:
Table of Contents

Advertisement

Setting Precautions
When using sample/hold of analog frequency reference, you cannot use the following commands at the same
time. Otherwise operation fault OPE03 (invalid multi-function input selection) will occur.
Acceleration/Deceleration Ramp Hold command
UP/DOWN command
Trim Control Increase/Decrease command
Application Precautions
When performing sample/hold of analog frequency reference, be sure to close the digital input for 100 ms
or more. If the sample/hold time is less than 100 ms, the frequency reference will not be held.
The frequency reference value that is held will be deleted when the power supply is turned OFF.

Switching Operation Source to Communication Option Card

The source of frequency reference and RUN command can be switched between a Communication option
card and the sources selected in b1-01 and b1-02. Set one of the parameters H1-01 to H1-05 (digital inputs S3
to S7 function selection) to 2 to enable operation source switch over.
If a RUN command is active, the switch over will not be accepted.
Related Parameters
Multi-function Digital Inputs (H1-01 to H1-05)
Set Value
Operation source selection: Option Card/ Inverter (ON: Inverter settings in b1-01 and b1-
2
02, OFF: Option Card)
Setting Precautions
To use the operation source switching function make the following settings:
Set b1-01 (frequency reference source) to a value different from 3 (option card).
Set b1-02 (RUN command source) to a value different from 3 (option card).
Set one of the parameters H1-01 to H1-05 to 2.

Jog Frequency with Direction Commands (FJOG/RJOG)

The FJOG/RJOG function operates the inverter at the jog frequency. It can be activated by using the terminal
ON/OFF operation. When using the FJOG/RJOG commands, there is no need to input the RUN command.
To use this function, set one of the parameters H1-01 to H1-05 (terminal S3 to S7 function selection) to 12
(FJOG command) or 13 (RJOG command).
Related Parameters
Parameter
No.
d1-17
Jog frequency reference
Function
Name
Control Methods
V/f
V/f
with
PG
Yes
Yes
Control Methods
Change
Factory
during
V/f with
Setting
Opera-
V/f
PG
tion
6.00 Hz
Yes
Q
Q
Open
Closed
6
Loop
Loop
Vector
Vector
Yes
Yes
Open
Closed
Loop
Loop
Vector
Vector
Q
Q
75