The relationship between the output frequency and the jump frequency reference is shown in
6
Setting Jump Frequency Reference Using an Analog Input
When parameter H3-09 (analog input A2 function selection) is set to A (jump frequency), the jump frequency
can be changed by the terminal A2 input value (respectively H3-05 and channel 3 of the AI-14B option card).
Setting Precautions
Set the jump frequencies according to the following formula: d3-01 ≥ d3-02 ≥ d3-03 > Analog input.
When parameters d3-01 to d3-03 are set to 0 Hz, the jump frequency function is disabled.
Adjusting Pulse Train Input Reference Values
If b1-01 is set to 4 and H6-01 is set to 0, the pulse train input is selected as the frequency reference source. Set
the pulse frequency that is equal to 100% reference in parameter H6-02, and then adjust the gain and bias
accordingly using H6-03 and H6-04.
30
6-
Name
Jump frequency 2
Jump frequency 3
Jump frequency width
Output frequency
Frequency reference descending
Jump
frequency 3
(d3-03)
Fig 6.35 Jump Frequency
Jump frequency
Max. output frequency
E1-04
Fig 6.36 Jump Frequency Setting Using an Analog Input
Factory
Setting
0.0 Hz
0.0 Hz
1.0 Hz
Jump frequency
width d3-04
Frequency reference ascending
Jump frequency
width d3-04
Jump frequency
width d3-04
Jump
Jump
frequency 2
frequency 1
(d3-02)
(d3-01)
Control Methods
Change
during
Open
V/f with
Opera-
V/f
Loop
PG
tion
Vector
No
A
A
A
No
A
A
A
No
A
A
A
Fig
Jump frequency reference
Multi-function analog input ter-
minal A2 input level
Closed
Loop
Vector
A
A
A
6.35.