The functions of DIP switch S1 and jumper CN15 are shown in the following table.
Table 2.10 DIP Switch S1 and Jumper CN15 Settings
Name
RS-485 and RS-422 terminating resis-
S1-1
tance
S1-2
Input method for analog input A2
CN15-
Multifunction analog output FM voltage/
CH1
current switch
CN15-
Multifunction analog output AM voltage/
CH2
current switch
Sinking/Sourcing Mode
The input terminal logic can be switched between sinking mode (0-V common) and sourcing mode (+24V
common) by using the terminals SN, SC, and SP. An external power supply is also supported, providing more
freedom in signal input methods.
Table 2.11 Sinking/Sourcing Mode and Input Signals
Internal Power Supply – Sinking Mode
Internal Power Supply – Sourcing Mode
Function
OFF: No terminating resistance
ON: Terminating resistance of 110 Ω
V: 0 to 10 V (internal resistance: 20 kΩ)
I: 4 to 20 mA (internal resistance: 250 Ω)
I: Current output
V: Voltage output
I: Current output
V: Voltage output
Setting
External Power Supply – Sinking Mode
External +24V
External Power Supply – Sourcing Mode
External +24V