Multifunction Digital Input Settings: H1-01 to H1-05 (Terminal S3 to S7)
PID Control Disable: "19"
If a multifunction input is set for this function it can be used to disable the PID function by switching the
input to ON.
The PID target value becomes the frequency reference value.
PID Control Integral Reset: "30"
Using this function the integral share value of the PID control can be reset by setting a multifunction input
to ON.
PID Control Integral Hold: "31"
Using this function the integral share value of the PID control can be hold by setting a multifunction input
to ON. The value will be hold as long as the input is ON.
PID Softstarter Disable: "34"
Using this function the PID softstarter can be disabled or enabled. It is disabled if the input is activated.
PID Input Characteristic Switch: "35"
Using this function the PID input characteristic can be inverted by setting a multifunction input to ON.