Omron VARISPEED F7 User Manual page 152

Vector control frequency inverter
Hide thumbs Also See for VARISPEED F7:
Table of Contents

Advertisement

Param-
Name
eter
Description
Num-
Display
ber
RTS control
Enables or disables RTS con-
ON/OFF
trol.
0: Disabled (RTS is always
H5-07
ON)
RTS Con-
1: Enabled (RTS turns ON
trol Sel
only when sending)
Unit Selec-
tion for
Selects the unit used for
MEMO-
MEMOBUS register 0025H
BUS regis-
H5-10
(output voltage monitor)
ter 0025H
0: 0.1 V units
MEMO-
1: 1 V units
BUS 0025H
Unit
* Set H5-01 to 0 to disable Inverter responses to MEMOBUS communications.
Pulse Train I/O: H6
Param-
Name
eter
Description
Num-
Display
ber
Pulse train
Selects the pulse train input
input func-
function
tion selec-
H6-01
0: Frequency reference
tion
1: PID feedback value
Pulse Input
2: PID target value
Sel
Pulse train
Sets the number of pulses in
input scaling
Hertz, that is equivalent to
H6-02
100% of the input item
Pulse In
selected in H6-01.
Scaling
Pulse train
Sets the input level according
input gain
to 100% of the input item
H6-03
selected in H6-01, when a
Pulse Input
pulse train with the frequency
Gain
set in H6-02 is input.
Pulse train
Sets the input level according
input bias
to 100% of the input item
H6-04
selected in H6-01, when the
Pulse Input
pulse train frequency is 0.
Bias
Pulse train
input filter
Sets the pulse train input delay
time
H6-05
filter time constant in seconds.
Pulse In
Filter
Pulse train
Select the pulse train monitor
monitor
output items (value of the
selection
part of U1-
H6-06
There are two types of moni-
Pulse Moni
tor items: Speed-related items
Sel
and PID-related items.
Pulse Moni
Sets the number of pulses out-
Scaling
put in hertz when the monitor
item is 100%.
H6-07
Sets H6-06 to 2, and H6-07 to
0, to make the pulse train
PO Scaling
monitor output synchronously
to the output frequency.
Setting
Factory
Range
Setting
0 or 1
1
0 or 1
0
Setting
Factory
Range
Setting
0 to 2
0
1000 to
1440
32000
Hz
0.0 to
100.0%
1000.0
-100.0
to
0.0%
100.0
0.00 to
0.10
2.00
s
1, 2, 5,
).
20, 24,
2
36
0 to
1440
32000
Hz
Control Methods
Change
during
V/f
Open
Closed
Opera-
V/f
with
Loop
tion
PG
Vector
No
A
A
A
No
A
A
A
Control Methods
Change
during
V/f
Open
Closed
Opera-
V/f
with
Loop
tion
PG
Vector
No
A
A
A
Yes
A
A
A
Yes
A
A
A
Yes
A
A
A
Yes
A
A
A
Yes
A
A
A
Yes
A
A
A
MEMO-
BUS
Page
Loop
Register
Vector
A
42BH
6-83
A
436H
-
MEMO-
BUS
Page
Loop
Register
Vector
6-7
A
42CH
6-30
6-7
A
42DH
6-30
A
42EH
6-30
A
42FH
6-30
A
430H
6-30
A
431H
6-81
A
432H
6-81
5-
5
51