Multi-Function Digital Inputs (H1-01 to H1-05)
Set
Value
19
PID control disable (ON: PID control disabled)
30
PID control integral reset (reset when reset command is input or when stopped during PID control)
31
PID control integral hold (ON: Integral hold)
34
PID soft starter
35
PID input characteristics switch
Multi-Function Analog Input (H3-09)
Set
Value
B
PID feedback
C
PID target value
Pulse Train Input (H6-01)
Set
Value
0
Frequency reference
1
PID feedback value
2
PID target value
PID Control Methods (b5-01)
There are four PID control methods. Select the method by setting parameter b5-01.
Set Value
PID output becomes the Inverter output frequency, and D control is used in the deviation (difference between PID target value and
1
feedback value.)
2
PID output becomes the Inverter output frequency, and D control is used in the PID feedback value.
PID output is added as compensation value of the Inverter output frequency, and D control is used in the deviation (difference
3
between PID target value and feedback value).
4
PID output is added as compensation value of the Inverter output frequency, and D control is used in the PID feedback value.
Function
Function
Function
Control Method
Control Methods
V/f
Open
Closed
V/f
with
loop
Loop
PG
Vector
Vector
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Control Methods
V/f
Open
Closed
V/f
with
loop
Loop
PG
Vector
Vector
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Control Methods
V/f
Open
Closed
V/f
with
Loop
Loop
PG
Vector
Vector
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
6
101
6-