Ct Or Related Abnormality - Daikin E-Series Service Manual

Hide thumbs Also See for E-Series:
Table of Contents

Advertisement

SiENBE12-620

5.20 CT or Related Abnormality

H8
remote control
Display
Outdoor Unit LED
A
Display
Method of
A CT or related error is detected by checking the compressor running frequency and CT-
Malfunction
detected input current.
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Service Diagnosis
1
2
3
4
5
4
4
1
The compressor running frequency is below 55 Hz and the CT input is below 0.1 V.
(The input current is also below 0.5 A.)
If this error repeats 4 times, the system will be shut down.
The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
Power transistor defective
Internal wiring broken or in poor contact
Reactor defective
Outdoor unit PCB defective