SiUS12-928_A
5.17 High Pressure Control in Cooling
F6
Remote
Controller
Display
Outdoor Unit LED
A
5
Display
Method of
High-pressure control (operation halt, frequency drop, etc.) is activated in cooling mode if the
Malfunction
temperature sensed by the outdoor heat exchanger thermistor exceeds the limit.
Detection
The temperature sensed by the outdoor heat exchanger thermistor rises above
Malfunction
The error is cleared when the temperature drops below
Decision
Conditions
The installation space is not large enough.
Supposed
Defective outdoor unit fan
Causes
Defective electronic expansion valve
Defective outdoor heat exchanger thermistor
Defective outdoor unit PCB
Defective stop valve
Dirty outdoor heat exchanger
Service Diagnosis
1
4
2
1
3
4
4
4
18 class
65°C (149°F)
47.5°C (118°F)
24/32 class
65°C (149°F)
49°C (120°F)
Troubleshooting
.
.
124