5.17 High Pressure Control in Cooling

F6
Remote
Controller
Display
Outdoor Unit LED
A
5
Display
Method of
High-pressure control (operation halt, frequency drop, etc.) is activated in cooling mode if the
Malfunction
temperature sensed by the outdoor heat exchanger thermistor exceeds the limit.
Detection
 The temperature sensed by the outdoor heat exchanger thermistor rises above
Malfunction
 The error is cleared when the temperature drops below
Decision
Conditions
 The installation space is not large enough.
Supposed
 Defective outdoor unit fan
Causes
 Defective electronic expansion valve
 Defective outdoor heat exchanger thermistor
 Defective outdoor unit PCB
 Defective stop valve
 Dirty outdoor heat exchanger
Service Diagnosis
1
4
2
1
3
4
4
4
18 class
65°C (149°F)
47.5°C (118°F)
24/32 class
65°C (149°F)
49°C (120°F)