Operation Shutdown Due To High-Pressure Control Or Freeze-Up Protection (Thermistor Activation) - Daikin FTXD60JV1B User Manual

Ftxd-j series, flx-j series, rxd-j series inverter pair
Hide thumbs Also See for FTXD60JV1B:
Table of Contents

Advertisement

SiBE04-101.book Page 90 Monday, October 15, 2001 3:08 PM
Troubleshooting
4.4
Operation Shutdown Due to High-Pressure Control or Freeze-Up Protection
(Thermistor Activation)
A5
Remote Controller
Display
Indoor unit LED
Display
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed Causes
Troubleshooting
Check No.1
Refer to P.119
90
High pressure control
During heating operations, the temperature detected by the indoor heat exchanger thermistor is used
for the high pressure control (operation stop)
The freeze protection control (operation halt) is activated during cooling operation according to the
temperature detected by the indoor unit heat exchanger thermistor.
High pressure control
During heating operations, the temperature detected by the indoor heat exchanger thermistor is above
67˚C
Freeze-Up protection
When the indoor unit heat exchanger temperature is below 0˚C during cooling operation.
Operation halt due to clogged air filter of the indoor unit.
Operation halt due to dust accumulation on the indoor unit heat exchanger.
Operation halt due to short-circuit.
Detection error due to faulty indoor unit heat exchanger thermistor.
Detection error due to faulty indoor unit PCB.
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check the air passage.
YES
Is there any short-circuit?
NO
Check the intake air filter.
YES
Is it very dirty?
NO
Check the dust accumulation on
the indoor unit heat exchanger.
YES
Is it very dirty?
NO
Check No. 1
Indoor unit heat exchanger
thermistor check
YES
Does it conform to the
thermistor characteristic
chart?
NO
SiBE04-101
Provide sufficient air passage.
Clean the air filter.
Clean the heat exchanger.
Replace the indoor unit PCB(1).
Replace the thermistor.
(R1170)
Service Diagnosis