SPECIFICATIONS
Table 9. Electrical Input
Nominal Voltage
Voltage Range
Nominal Frequency
Frequency Range
Default Frequency
Maximum Input Current at
Nominal Utility Voltage
Noise Filtering
Connections
Input Power Factor
Input Mode
Table 10. Electrical Output
Regulation
Nominal Outputs
Output Overload
Voltage Waveform
Output Receptacles
Full Output
92
Eaton 9140 UPS (7.5–10 kVA) User's Guide
200/208/220/230/240V auto-sensing
60 Hz (50 Hz for hardwired model, 220–240V)
(not applicable for hardwired models)
MOVs and line filter for normal and common mode noise
3-meter IEC 309-60A power cord or hardwired
Single-phase or three-phase (three-phase option on hardwired models only)
Nominal output voltage ±2% Static, ±10% Dynamic
(voltage configurable or auto-sensing)
100–110%: activates Overload alarm
110–130%: load transfers to Bypass mode after 1 minute
130–150%: load transfers to Bypass mode after 1 second
>150%: load transfers to Bypass mode after 100 ms
Normal mode: Sine wave; <3% THD with linear load;
<5% with nonlinear load
Plug-Receptacle Models:
(4) C19,
each with 20A circuit breaker
IEC 309-60A
S
164201622 Rev 3 www.eaton.com/powerquality
160–253V, 174–288V
50/60 Hz auto-sensing
45–65 Hz
48A
>0.99
200/208/220/230/240V
45/48/45/43/41A
9/10/10/10/10 kVA
7.2/8/8/8/8 kW
Hardwired Models:
(3) C19 and (1) dual C13,
each with 20A circuit breaker
Hardwired