UPS MAINTENANCE
86
Eaton 9140 UPS (7.5–10 kVA) User's Guide
Pull the battery trays out onto a flat, stable surface. The battery trays are unsupported when
you pull them out of the UPS.
2.
Push down and hold a battery tray lock to unlock a tray. Pull the
battery tray slowly out onto a flat, stable surface; use two hands to
support the tray. See Figure 45.
The UPS display indicates within 5–60 seconds that a battery is
disconnected. However, if an optional EBM is installed, the display
does not indicate a disconnected battery.
Repeat for each battery tray. See "Recycling the Used Battery or
UPS" on page 89 for proper disposal.
3.
Slide the new battery trays into the cabinet. Push each tray in until
the battery tray lock on the handle catches to lock the tray in place.
4.
Replace the UPS front cover and tighten the two front cover
screws.