Table 5. User Settings (continued)
Description
Language
XCP Load Control
Upper Bypass V
Lower Bypass V
Bypass Freq Dev
(Bypass Frequency Deviation Limits)
Qualify Bypass
Allow Bypass
Set Baud Rate
Set Site (Wiring) Fault
Contact Config*
* Changes to these options should be made before turning on the UPS (while the UPS is in Standby mode); otherwise,
the changes do not take effect.
Eaton 9140 UPS (7.5–10 kVA) User's Guide
Available Settings
Select Language: <English> <Spanish>
<French> <German> <Finnish>
[Enabled][Disabled]
+0 through +20% (1% increments)
-0 through -20% (1% increments)
1 through 5 Hz (1 Hz increments)
NOTE This value sets the limits from 1 Hz to
5 Hz of the nominal output configuration.
[Enabled][Disabled]
NOTE This setting enables or disables the
bypass qualification rules. When set to
Disabled, Bypass is always available.
[Enabled][Disabled]
Port 1 (RS232): [19200] [9600] [2400] [1200]
Port 2 (SERVICE): [19200] [9600] [2400] [1200]
[Enabled][Disabled]
Contact Usage: [REPO][ROO][Disabled]
Contact Type: [N/O][N/C]
S
164201622 Rev 3 www.eaton.com/powerquality
OPERATION
Default Setting
English
Enabled
+20%
-20%
3 Hz
Enabled
Enabled
9600
Disabled
REPO
N/O
65