SPECIFICATIONS
Table 12. Battery
Type
Monitoring
Configuration
Charging (in minutes)
(10 kVA models)
Charging (in minutes)
(7.5 kVA models)
NOTE Charging times are approximate and are to 80% usable capacity at nominal line voltage after full load discharge.
Table 13. Battery Runtimes (in Minutes)
Load
(10 kVA Models)
100% Load
75% Load
50% Load
25% Load
Load
(7.5 kVA Models)
100% Load
75% Load
50% Load
25% Load
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
94
Eaton 9140 UPS (7.5–10 kVA) User's Guide
UPS Internal
+1 EBM
Batteries
Sealed, maintenance‐free, valve‐regulated, lead‐acid
Advanced monitoring for earlier failure detection and warning
266
336
215
367
UPS Internal
+1 EBM
Batteries
5
12
7
17
12
27
31
61
UPS Internal
+1 EBM
Batteries
8.5
23.5
12
30
22
51.5
48
94
S
164201622 Rev 3 www.eaton.com/powerquality
+2 EBMs
+3 EBMs
(32) 12V, 5 Ah
368
398
390
416
+2 EBMs
+3 EBMs
27
35
35
46
52
69
99
138
+2 EBMs
+3 EBMs
37.5
53
52
69
78.5
98.5
116
>120
+4 EBMs
419
440
+4 EBMs
45
60
90
181
+4 EBMs
65.5
86.5
111
>180