INSTALLATION
Table 1. UPS Input Wiring Specifications
UPS Terminal
Terminal
Block
Position
Input
1
2
Use 13.3 mm
(6 AWG) 90_C copper wire minimum. For ease of installation, use appropriately sized ferrules on the end
of each wire.
2
For single-phase 208V only, in North America and Japan, utility L2 connects to UPS neutral; for most other countries
(200, 220-240V), utility neutral connects to UPS neutral.
3
The ground screw on the input terminal block can be used for input ground if an appropriate ring lug is available.
54
Eaton 9140 UPS (7.5–10 kVA) User's Guide
9.
Connect the input and ground wires to the input terminal block
according to Figure 32 and Table 1.
UPS Wire Function
1
L1 In
2
L2 In
3
L3 In
4
Neutral In
5
Input Ground
10. Connect the input bypass and ground wires to the input bypass
terminal block according to Figure 33 and Table 2.
Figure 33. UPS Input Bypass Terminal Block
S
164201622 Rev 3 www.eaton.com/powerquality
L1 In
L2 In
L3 In
Neutral In
Figure 32. UPS Input Terminal Block
Terminal Wire
Size Rating
2
13.3 mm
(6 AWG)
2
3
Line In Neutral In
L1-JP
Input Ground
Tightening
1
Torque
1.8 Nm (16 lb in)
Input Bypass
Ground