Eaton Powerware 9140 User Manual page 61

Powerware series 7.5–10 kva
Hide thumbs Also See for Powerware 9140:
Table of Contents

Advertisement

Table 2. UPS Input Bypass Wiring Specifications
UPS Terminal
Terminal
Block
Position
Input Bypass
2
* Use 13.3 mm
(6 AWG) 90_C copper wire minimum. For ease of installation, use appropriately sized ferrules on the end
of each wire.
Eaton 9140 UPS (7.5–10 kVA) User's Guide
UPS Wire Function
1
L1-JP
2
Line In
3
Neutral In
4
Input Bypass Ground
11. Connect the output and ground wires to the output terminal block
according to Figure 34 and Table 3.
Terminal Wire
Size Rating*
2
13.3 mm
(6 AWG)
Line/L1
Out
Figure 34. UPS Output Terminal Block
S
164201622 Rev 3 www.eaton.com/powerquality
INSTALLATION
Tightening
Torque
1.8 Nm (16 lb in)
Neutral or L2 Out
Output
Ground
55