INSTALLATION
46
Eaton 9140 UPS (7.5–10 kVA) User's Guide
NOTE DO NOT protect laser printers with the UPS because of the exceptionally high power
requirements of the heating elements.
NOTE Verify that the total equipment ratings do not exceed the UPS capacity to prevent an
overload alarm.
4.
Plug the equipment to be protected into the UPS output
receptacles, but do not turn on the protected equipment (see
Figure 27).
5.
Make any necessary provisions for cord retention and strain relief.
6.
If an emergency power-off (disconnect) switch is required by local
codes, see "REPO and ROO Installation" on page 58 to install the
REPO switch before powering on the UPS.
If you are not required to install a REPO switch, you can install an
optional remote on/off (ROO) switch (see page 58).
7.
Switch all circuit breakers to the ON (
8.
Plug the UPS input power cord into an IEC 309-60A power outlet.
The
indicator flashes, indicating the UPS is in Standby mode
with the equipment offline. The fans run and the LCD illuminates
and displays the UPS startup screens.