Alarm or Condition
Power is not available at the
UPS output receptacles.
The UPS does not start.
The UPS does not turn off.
The UPS is powered (front
panel and fans are on), but
some or all of the protected
equipment is not on.
Battery test failed.
Battery test did not run.
Eaton 9140 UPS (7.5–10 kVA) User's Guide
Possible Cause
The UPS is in Standby mode.
The main utility breaker is off.
The power cord is not connected
correctly (plug-receptacle models).
The electronics module is being
replaced.
The batteries or electronics module
is being replaced.
The equipment is not connected to
the UPS correctly.
The REPO switch is active or the
REPO connector is missing.
Circuit breakers for UPS
receptacles are in the OFF position.
UPS receptacles have been turned
off by power management software
or a communication card.
The UPS is in Standby mode.
The batteries need service.
Load was less than 10% of rated
capacity when the battery test
started. Battery test report shows
CANCELLED, then changes to TEST
SCHED during the next appropriate
stage in the charging cycle.
User cancelled the battery test
through the front panel. Battery test
report shows CANCELLED.
Battery charge cycle has not
completed.
S
Action
Supply power to the connected equipment:
Turn the UPS on by selecting MENU from the
system status screen, then select CONTROL,
OUTPUT CONTROL, UPS TO ONLINE, and OK to
confirm.
Verify that the main utility breaker is on.
Check the power cord connections.
Complete the replacement procedure before
starting the UPS, or remove the utility power.
Complete the replacement procedure before
shutting down the UPS.
Verify that the equipment is plugged into the
UPS receptacles. For hardwired models,
contact a qualified electrician to check
connections to the power source.
Reset the REPO switch and restart the UPS.
Verify that the REPO connector is present.
Switch UPS receptacle circuit breakers to the
ON position.
Modify the settings in the power management
software or the communication card (refer to
the individual user's guide).
Use the front panel to return the UPS to Normal
mode.
Contact your service representative.
The UPS automatically reschedules the battery
test.
Reschedule the battery test if necessary.
Wait 48 hours.
164201622 Rev 3 www.eaton.com/powerquality
TROUBLESHOOTING
97