Table 2-8: Configuration > Doors: > 1 > Outputs Tab > Reader Led Dialog Box Fields - Honeywell NetAXS-123 User Manual

Access control unit
Hide thumbs Also See for NetAXS-123:
Table of Contents

Advertisement

Configuring via the Web Server
Configuring the Doors
: Use the descriptions in
Steps
LED:
Table 2-8: Configuration > Doors: > 1 > Outputs Tab > Reader LED Dialog Box
Setting
Name
Pulse Time
Time Zones
Latching
Interlock
TZ Card Toggle
First Card Rule
50
www.honeywell.com
Table 2-8
Fields
Description
Enter a unique name to identify the device.
Specifies the duration for which the device will assume abnormal
status. For example, it specifies how long a horn will sound or a door
strike will remain released. The maximum number of hours is 1.
When the hour field is blank, the maximum number of minutes is 59.
When 1 is entered in the hour field, the maximum number of minutes
is 45 and the maximum number of seconds is 59.9. The sum of all
three units comprises the pulse time. Note that you can express
seconds in tenths of a second.
Specifies two schedules:
Energized
automatically energized.
Disable Interlock
programmed interaction between selected inputs and outputs,
will be disabled. During the selected Time Zone this point
ignores all interlock actions to it, effectively disabling it from
being a Reacting Component during the Time Zone. Outside of
the Time Zone the point will react to interlocks as expected.
Toggles the state of the outputs between energized and de-energized
status upon every activation (code use, interlock, or manual pulse).
Enables you to disable the interlock, or programmed interaction
between two points. When enabled, this point ignores all interlock
actions to it, effectively disabling it from being a Reacting
Component.
Requires, like the First Card Rule, a valid card read within the time
zone to enable the time zone (period in which doors are unlocked) to
take effect. Unlike the First Card Rule, however, the user can swipe
the card a second time to return the doors to a locked state. Note that
both TZ Card Toggle and First Card Rule cannot be enabled at the
same time. Appears only when the Lock option is selected.
Requires a valid card read within the time zone to enable the time
zone (period in which doors are unlocked) to take effect. Note that
both TZ Card Toggle and First Card Rule cannot be enabled at the
same time. Appears only when the Lock option is selected.
to configure each individual lock or Reader
– sets the period during which the output is
– sets the period during which the interlock, a

Hide quick links: