2.6 Communication Wiring

The PW6K1ICE communicates with PW6K1R1E through the Ethernet. In the event
of communication loss, all readers connected to the PW6K1R1E must be programmed
to the "locked" option in the Offline mode menu.

2.7 Reader Wiring

The first reader port supports Wiegand, magnetic stripe, or 2-wire RS-485 electrical
interfaces.
The second reader port supports Wiegand or magnetic stripe electrical interfaces.
Power to the first reader is 12VDC and its current is limited to 150mA. The second
reader may be powered from the auxiliary power output on TB5-1 and TB5-2.
Readers that require different voltage or have high current requirements should be
powered separately. Refer to the manufacturer's specifications for cabling
requirements. In the 2-wire LED mode, the Buzzer output is used to drive the second
LED. Reader port configuration is set via the host software.
Figure 2-4: First Reader Port Wiring
Figure 2-5: Second Reader Port Wiring
PW6K1R1E Configuration and Installation Guide, Document 800-07986V1, Revision A
RED (1)
VO
LED
BRN (4)
BZR
ORG (5)
CLK/D1
WHT (3)
DAT/D0
GRN (2)
GND
BLK (6)
FIRST READER PORT
DATA1/DATA0 OR CLOCK/DATA
BLK (6)
BRN (4)
ORG (5)
WHT (3)
GRN (2)
RED (1)
SECOND READER PORT
DATA1/DATA0 OR CLOCK/DATA
PW6K1R1E Wiring and Setup
LED
BZR
CLK/D1
DAT/D0
VO
GND

Communication Wiring