Earth Fault Resistance; Calculating Current Draw And Standby Battery; 1: Worksheet Requirements; Filling In The Current Draw Worksheet, Table 2.4 Or Table 2.5 - Honeywell SILENT KNIGHT 5895XL Manual

Intelligent power module
Hide thumbs Also See for SILENT KNIGHT 5895XL:
Table of Contents

Advertisement

Before You Begin Installing

2.4 Earth Fault Resistance

Table 2.2 lists the earth fault resistance detection, in ohms, for each applicable terminal on the FACP.
Function
Flexput
Notification
Circuits
SBUS
Communication
SBUS Power
Used for Class A
Installations

2.5 Calculating Current Draw and Standby Battery

This section contains instructions and tables for calculating current draws and standby battery needs.
2.5.1 Worksheet Requirements
The following steps must be taken when determining 5895XL current draw and standby battery requirements.

Filling in the Current Draw Worksheet, Table 2.4 or Table 2.5

1.
For the 5895XL, the worst case current draw is listed for the panel, addressable devices, and SLC expanders. Fill in the number of
addressable devices and expanders that will be used in the system and compute the current draw requirements for alarm and standby.
2.
Add up the current draw for all auxiliary devices and record in the table at Line B.
3.
Add up all notification appliance loads and record in the table at Line C.
4.
For notification appliances and auxiliary devices not mentioned in the manual, refer to the device manual for the current ratings.
5.
Make sure that the total alarm current calculated, including current for the panel itself, does not exceed 6.0 A. This is the maximum
alarm current allowable.
6.
Complete the remaining instructions in the table for determining battery size requirements.
12
Terminal
Terminal Label
Number
4
X
5
O
6
X
7
O
8
X
9
O
10
X
11
O
12
X
13
O
14
X
15
O
16
B
17
A
SBUS OUT
18
+
19
-
20
B
21
A
22
+
23
-
Table 2.2 Earth Fault Resistance Values by Terminal
Low Biased
High Trip
High Restore
-
I/O 6
0
-
I/O 5
0
-
I/O 4
0
-
I/O 3
0
-
I/O 2
0
-
I/O 1
0
-
-
0
-
-
-
SBUS IN
0
-
5895XL Manual — P/N 151142-L8:M 2/15/2022
Earth Fault Resistance
High Biased
Low Trip
Low Restore
-
0
0
-
-
0
0
-
-
0
0
-
-
0
0
-
-
0
0
-
-
0
0
-
-
0
-
0
0
-
-
0
-
0
-
0
0
-
-
0
0
-
0
-
0
-
0
-
0
-
0
-
0
0
-
0
0
0
-
0