Toshiba TOSVERT VF-A7 Instruction Manual page 217

The new generation high-performance inverter 200v class 0.4- 90kw 400v class 0.75-280kw
Hide thumbs Also See for TOSVERT VF-A7:
Table of Contents

Advertisement

[16] Functions for lift (2/2)
Communi
Title
cation No
0340
Heavy load torque during fixed speed in reverse direction

0341
Automatic light-load high-speed operation frequency

[17] Commercial/inverter switching function
Communi
Title
Function
cation No
Output signal selection of

0354
commercial power/inverter
switching
Commercial power/inverter

0355
switching frequency

0356
Inverter side switching waiting time Model dependent 10.00 [s]
Commercial power side
0357

switching waiting time
Commercial power switching

0358
frequency holding time
[18] PID control
Communi
Title
Function
cation No

0360
Signal selection of PID control 0: PID control disabled, 1: VI/II, 2: RR, 3: RX, 4: RX2
0361
Delay filter


0362
Proportional (P) gain
0363
Integral (I) gain


0364
PID deviation upper limit
0365
PID deviation lower limit


0366
Differential (D) gain
[19] Speed feedback/positioning control
Communi
Title
Function
cation No

0367
Number of PG input pulses
0368
Number of PG input phases

0369
PG disconnection detection


0370
Electronic gear
0371
Position loop gain


0372
Positioning completion range 1 4000
0373
Frequency limit at position control 1 8000 [Hz/s], 8001: disabled

(Reference section): Refer to the inverter's individual manual.
Function
Adjustment range
0 250 [%]
30.0  [Hz]
Adjustment range
0: OFF, 1: Automatic switching in case of trip
2: Commercial power switching frequency setting
enabled
3: Both (1+2)
0  [Hz]
0.37 10.00 [s]
0.1 10.0 [s]
Adjustment range
0 255
0.01 100.0
0.01 100.0
0 50 [%]
0 50 [%]
0.00 2.55
Adjustment range
1 9999
1: Single-phase input, 2: Two-phase input
0: Disabled, 1: Enabled
100 to 4000 pulses/rotation
0.0 100.0
Sensorless vector/vector with sensor ( valid,
Min. unit (panel/
Default
Write during
Speed
communication)
setting
running
control
1
100
Enabled
/
0.01/0.01
80.0
Enabled
/
Min. unit (panel/
Default
Write during
Speed
communication)
setting
running
control
0
Disabled
/
0.01/0.01
60.0
Enabled
/
0.01/0.01
See J-28
Enabled
/
0.01/0.01
0.62
Enabled
/
0.1/0.01
2.0
Enabled
/
Min. unit (panel/
Default
Write during
Speed
communication)
setting
running
control
0
Enabled
/
0
Enabled
/
0.01/0.01
0.1
Enabled
/
0.01/0.01
0.1
Enabled
/
1/0.01
50
Enabled
/
1/0.01
50
Enabled
/
0.01/0.01
0
Enabled
/
Min. unit (panel/
Default
Write during
Speed
communication)
setting
running
control
1/1
500
Disabled
/
2
Disabled
/
0
Disabled
/
1/1
1000
Disabled
0.1/0.01
4.0
Enabled
1/1
100
Enabled
1/1
800
Disabled
:invalid)
Vector control
V/f
Reference
Torque
Position
Constant
section
control
control
Vector control
V/f
Reference
Torque
Position
Constant
section
control
control
/
6.16
/
6.16
/
6.16
/
6.16
/
6.16
Vector control
V/f
Reference
Torque
Position
Constant
section
control
control
Vector control
V/f
Reference
Torque
Position
Constant
section
control
control
/
/
/
/
/
/
/
/
/
/