Toshiba TOSVERT VF-A7 Instruction Manual page 224

The new generation high-performance inverter 200v class 0.4- 90kw 400v class 0.75-280kw
Hide thumbs Also See for TOSVERT VF-A7:
Table of Contents

Advertisement

[28] Protection functions
Communi
Title
Function
cation No

0600
Motor overload protection level #1 10 100 [%]

0601
Stall prevention level
0602
Selection of inverter trip holding


0603
Emergency stop
Emergency DC injection

0604
braking control time
0605
Output phase failure detection 0: Disabled, 1: Enabled

0606
Overload reduction start-up frequency 0.0 30.0 [Hz]


0607
Motor 150%-overload time limit 10 2400 [s]
Relay injection timing for

0608
rush-current suppression
0609
Mode of rush-current suppression relay 0: Standard, 1: in relation to ST

0610
Low current trip


0611
Low current detection level

0612
Low current detection time
Detection of output short-
0613

circuit during start-up
Adjustment of detection pulse for
0614
output short-circuit during start-up 1 100 [ s]


0615
Over-torque trip
Over-torque detection level

0616
during power running
Over-torque detection level
0617

during regeneration
0618
Over-torque detection time


0620
Cooling fan control mode

0621
Cumulative operation time alarm setting 0.1 999.9 [ 100h]
0622
Abnormal speed detection filter 0.01 100.0 [s] (*1)

0623
Over-speed detection frequency range 0: Disabled, 0.1 30.0 [Hz]


0624
Speed drop detection frequency range 0: Disabled, 0.1 30.0 [Hz]
Over-voltage stall protection

0625
level (high response)
0626
Over-voltage stall protection level 50 250 [%]

0627
Under-voltage trip mode


0628
Under-voltage detection time 0.00 10.00 [s]

0629
Under-voltage stall level
0630
System-supporting sequence(B-timer)

0631
Position deviation limit


0632
Brake release inhibition time after run 0.00: Setting of  is valid, 0.01 2.50 [s]
The trip selection at the VI/II

0633
low-level input
(*1): Set a time longer than the acceleration/deceleration time.
(Reference section): Refer to the inverter's individual manual.
Adjustment range
0 199 [%], 200: Disabled
0: Cleared if power is turned off
1: Held even if power is turned off
0: Coast stop 1: Deceleration stop
2: Emergency DC injection braking stop
3: Coast stop without FL output
4: Deceleration stop without FL output
5: Emergency DC injection braking without FL output
0.0 10.0 [s]
0.3 2.5 [s]
0: Disabled, 1: Enabled
0 100 [%]
0 255 [s]
0: Standard
1: Only one time at power injection or at first start after reset
0: Disabled, 1: Enabled
0 250 [%]
0 250 [%]
0.0 100.0 [s]
0: Automatic, 1: Always ON
50 250 [%]
0: Disabled, 1: Enabled
50 100 [%]
0.0: Invalid, 0.1 10.0 [s]
0.1 6553
0 100
Sensorless vector/vector with sensor ( valid,
Min. unit (panel/
Default
Write during
Speed
communication)
setting
running
control
1/0.01
100
Enabled
/
1/0.01
150
Enabled
/
0
Disabled
/
0
Disabled
/
0.1/0.01
0.1
Enabled
/
0
Disabled
/
0.01/0.01
6.0
Enabled
/
1/1
600
Enabled
/
0.1/0.01
0.3
Disabled
/
0
Disabled
/
0
Disabled
/
1/0.01
0
Enabled
/
1/1
0
Enabled
/
0
Disabled
/
1/1
50
Disabled
/
0
Enabled
/
1/0.01
150
Enabled
/
1/0.01
150
Enabled
/
0.1/0.01
0.5
Enabled
/
0
Enabled
/
0.1/0.1
175.0
Enabled
/
0.01/0.01
10.00
Enabled
/
0.01/0.01
0.0
Enabled
/
0.01/0.01
0.0
Enabled
/
1/0.01
135
Enabled
/
1/0.01
130
Enabled
/
0
Disabled
/
0.01/0.01
0.03
Disabled
/
1/0.01
75
Enabled
/
0.1/0.01
0.0
Enabled
/
0.1/0.1
16
Disabled
0.01/0.01
0.00
Disabled
/
1/1
0.00
Enabled
/
:invalid)
Vector control
V/f
Reference
Torque
Position
Constant
section
control
control
/
/
5.13
/
/
6.25.2
/
/
6.25.3
/
/
6.25.4
/
/
6.25.4
/
/
/
/
5.13
/
/
5.13
/
/
/
/
/
/
6.25.7
/
/
6.25.7
/
/
6.25.7
/
/
6.25.8
/
/
6.25.8
/
/
6.25.9
/
/
6.25.9
/
/
6.25.9
/
/
6.25.9
/
/
6.2510
/
/
6.25.11
/
/
/
/
/
/
/
6.13.5
6.13.5
/
/
6.25.13
/
/
6.25.14
/
/
6.25.15
/
/
/
/
/
/
/

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents