[33] Communication function(1/2)
Communi
Title
Function
cation No
0800
Communication rate (common serial) 0: 1200, 1: 2400, 2:4800, 3: 9600
0801
Parity (common serial/RS485)
0802
Inverter number(common)(*1) 0 255
Communication time-out
0803
(common serial/RS485)
Communication time-out action
0804
(common serial /RS485)
Communication waiting time
0805
(common serial)
Inter-drive communication
0806
(common serial)
0810
Frequency point selection
0811
Point #1 setting
0812
Point #1 frequency
0813
Point #2 setting
0814
Point #2 frequency
0820
Communication rate (RS485) 0: 1200, 1: 2400, 2: 4800, 3: 9600, 4: 19200, 5: 38400
0821
RS485 wiring system
0825
RS485 communication waiting time 0.00: Normal, 0.01 2.00 [s]
Inter-drive communication (RS-
0826
485)
0830
Data type
0831
Input reference setting #1
0832
Input reference setting #2
0833
Input reference setting #3
0834
Input reference setting #4
0835
Input reference setting #5
0836
Input reference setting #6
0841
Monitor output setting #1
0842
Monitor output setting #2
0843
Monitor output setting #3
0844
Monitor output setting #4
0845
Monitor output setting #5
0846
Monitor output setting #6
0850
Mode at communication error 0 4
0851
Communication error detection time 0 1000
0860
Receiving address
0861
Transmitting address
(*1): To be only monitoring available when using S20 option.
(*2): Parameters , , , , and can be reflected at resetting (power OFF
(Reference section): Refer to the inverter's individual manual.
Adjustment range
0: No parity, 1: Even parity, 2: Odd parity
0: OFF, 1 100 [s]
0 8
0.00: Normal, 0.01 2.00 [s]
0: Normal, 1: Frequency reference, 2: Output frequency,
3: Torque reference, 4: Output torque
0: Invalid, 1: Common serial, 2: RS485,
3: Communication add-on cassette option
0 100 [%]
0.0 [Hz]
0 100 [%]
0.0 [Hz]
0: 2-line system, 1: 4-line system
0: Normal, 1: Frequency reference, 2: Output frequency,
3: Torque reference, 4: Output torque
0, 1
0 16
0 16
0 16
0 16
0 16
0 16
0 16
0 16
0 16
0 16
0 16
0 16
0 1023
0 1023
Sensorless vector/vector with sensor ( valid,
Min. unit (panel/
Default
Write during
Speed
communication)
setting
running
control
3
Enabled
/
1
Enabled
/
1/1
0
Enabled
/
1/1
0
Enabled
/
8
Enabled
/
0.01/0.01
0.00
Enabled
/
0
Enabled
/
0
Enabled
/
1/0.01
0
Enabled
/
0.01/0.01
0.0
Enabled
/
1/0.01
100
Enabled
/
0.01/0.01
80.0
Enabled
/
3
Enabled
/
1
Enabled
/
0.01/0.01
0.00
Enabled
/
0
Enabled
/
1/1
0
Enabled
/
1/1
0
Enabled
/
1/1
0
Enabled
/
1/1
0
Enabled
/
1/1
0
Enabled
/
1/1
0
Enabled
/
1/1
0
Enabled
/
1/1
0
Enabled
/
1/1
0
Enabled
/
1/1
0
Enabled
/
1/1
0
Enabled
/
1/1
0
Enabled
/
1/1
0
Enabled
/
1/1
0
Enabled
/
1/1
200
Enabled
/
1/1
0
Enabled
/
1/1
0
Enabled
/
ON).
:invalid)
Vector control
V/f
Reference
Torque
Position
Constant
section
control
control
/
/
6.30
/
/
6.30
/
/
6.30
/
/
6.30
/
/
6.30
/
/
6.30
/
/
6.30
6.30
6.30
6.30
6.30
6.30
/
/
6.30
/
/
6.30
/
/
6.30
/
/
6.30
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/