Download Print this page

HP c-Class Overview page 44

Hp bladesystem c-class infrastructure
Hide thumbs Also See for c-Class:

Advertisement

QuickSpecs
Technical Specifications
Enclosure Unit - Tower
Enclosure Unit - Tower
Enclosure Unit - Tower
Enclosure Unit - Tower
Model
Model
Model
Model
NOTE: Operating temperature has an altitude derating of 1.8° F (1° C) per 1,000 ft (304.8 m). No
NOTE:
NOTE:
NOTE:
direct sunlight. Upper operating limit is 10,000 ft (3,048 m) or 70Kpa/10.1 psia. Upper non-operating
limit is 30,000 ft (9,144 m) or 30.3 KPa/4.4 psia. Storage maximum humidity of 95% is based on a
maximum temperature of 113° F (45° C). Altitude maximum for storage is 70 KPa.
NOTE: For additional Technical Specifications regarding the c3000 Server Blade Enclosure, please see:
NOTE:
NOTE:
NOTE:
http://h18000.www1.hp.com/products/quickspecs/12790_div/12790_div.html
Dimensions
Dimensions
Dimensions (H x W x D)
Dimensions
(with bezel)
Weight
Weight
Weight
Weight
(approximate)
Input Requirements
Input Requirements
Input Requirements
Input Requirements
(per AC power supply)
BTU Rating
BTU Rating
BTU Rating
BTU Rating
Power Specifications
Power Specifications
Power Specifications
Power Specifications
Power Supply Output
Power Supply Output
Power Supply Output
Power Supply Output
(per power supply)
System Inlet Temperature Operating
System Inlet Temperature
System Inlet Temperature
System Inlet Temperature
DA - 12517
Worldwide — Version 19 — September 15, 2008
21.29 x 13.48 x 34.43 in (54.08 x 34.24 x 87.45 cm)
Maximum
(all server blades and
interconnects installed)
Minimum
(2 power supplies & 4
fans, no server blades nor
interconnects installed)
Rated Line Voltage
Rated Input Current
Rated Input Frequency
Maximum per power
supply
To review typical system power ratings use the Power Calculator which is
available via the online tool located at URL:
www.hp.com/go/bladesystem/powercalculator
Rated Steady-State Power 800 W (at 100 VAC),
Maximum Peak Power
Non-operating
HP BladeSystem c-Class Infrastructure
HP BladeSystem c-Class Infrastructure
HP BladeSystem c-Class Infrastructure
HP BladeSystem c-Class Infrastructure
342 lb (155 kg)
192 lb (87.09 kg)
90 - 132 VAC
180 - 264 VAC
9.3 A (at 100 VAC)
9.7 A (at 110 VAC)
7.8 A (at 200 VAC)
7.2 A (at 208 VAC)
6.8 A (at 220 VAC)
6.2 A (at 240 VAC)
47 to 63 Hz
2728 BTU/hr (at 100 VAC)
3069 BTU/hr (at 120VAC)
4092 BTU/hr (at 200 to 240 VAC)
900 W (at 120 VAC)
1200 W (at 200 to 240 VAC)
880 W (at 100 VAC),
990 W (at 120 VAC)
1350 W (at 200 to 240 VAC
10° to 35°C (50° to 95°F) at sea level with an
altitude derating of 1.0°C per every 305 m (1.8°F
per every 1000 ft) above sea level to a maximum
of 3050 m (10,000 ft), no direct sustained
sunlight. Maximum rate of change is 10°C/hr
(18°F/hr). The upper limit may be limited by the
type and number of options installed. System
performance may be reduced if operating with a
fan fault or above 30°C (86°F).
-30° to 60°C (-22° to 140°F). Maximum rate of
change is 20°C/hr (36°F/hr).
Page 44

Advertisement

loading

This manual is also suitable for:

Bladesystem c7000Bladesystem c3000