COMMUNICATION

Control Terminals

54
EATON Powerware

Powerware LanSafe Power Management Software

Each Powerware 9155 UPS ships with Powerware LanSafe Power Management
Software and an interface cable. To begin installing Powerware LanSafe software,
see the instructions accompanying the Software Suite CD.
NOTE Use only the supplied communication cable to connect the UPS to your computer.
Powerware LanSafe software provides up-to-date graphics of UPS power and system
data and power flow. It also gives you a complete record of critical power events, and
it notifies you of important UPS or power information. If there is a power outage and
the Powerware 9155 UPS battery power becomes low, Powerware LanSafe software
can automatically shut down your computer system to protect your data before the
UPS shutdown occurs.
The cables should be connected to the control terminals with a mating connector.
Input and output terminals have a functional isolation from terminal to terminal. They
are connected to the UPS chassis through individual 1 MΩ resistors.
UPS
Connectors
(see Figure 36 on
page 49)
NOTE If using a semiconductor switch type, pay attention to the proper polarity. A relay or other
mechanical control is preferred.
®
9155 UPS (8–15 kVA) User's Guide
2
+ Polarity
– Polarity
1
2
+ Polarity
– Polarity
1
2
REPO Normally Open
1
2
REPO Normally Closed
1
Common
3
Normally Closed
2
1
Normally Open
Figure 43. External Control Terminal Connections
S
164201553 Rev F www.powerware.com
Signal Input 1 (programmable)
Signal Input 2 (programmable)
Relay Output