Table 9. User Settings
Description
Set Date and Time
Display Contrast
Change Language
Relay Config
Signal Inputs
Serial Port Config
Parallel Operation Settings
Modem Config
Start Screen
User Password
Audible Alarms
Battery Charging
Automatic Battery Tests
Full Power Battery Test
Number of Battery Strings
Battery Capacity
Battery Low Alarm Level

User Settings

The following table displays the options that can be changed by the user.
NOTE Changes to the output voltage or frequency options should be made before turning on the UPS;
otherwise, the changes do not take effect.
Available Settings
Set Month
Date: mm/dd/yyyy
Time: 24:00
Adjust contrast with up/down arrow buttons
Select Language: <English>
Elegir idioma <Español>
Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or [X-Slot 2-1/2/3/4]
Setup: [empty] [On Battery] [Summary Alarm] [On Bypass] [UPS ok]
[custom]
[empty] [Logic]
(see "Programmable Signal Inputs" on page 56)
Port: [X-Slot-1] [X-Slot-2/Serv]
Speed: [19200] [9600] [2400] [1200]
Refer to the Powerware 9155 Parallel UPS (8–15 kVA) User's Guide.
Modem Installation
Set Modem Call Events
Set Modem Init String
Set Modem Call Command
Set Modem Communication Password
Eaton Powerware logo
Mimic screen
Enabled/Disabled
If Enabled is selected, the password is USER.
Normal Sound/Disabled
ABM cycling/constant
Enabled/Disabled
Enabled automatically runs the battery test once a month.
Enabled/Disabled
0 through 22
(see "Configuring the UPS for EBMs" on page 64)
1 through 65535 watts per cell
1.750 through 1.950 volts per cell
®
EATON Powerware
9155 UPS (8–15 kVA) User's Guide
Default Setting
01/01/2003
00:00
Moderate
English
Alarm 1: empty
X-Slots (1 or 2)
#1: UPS ok
#2: On Bypass
#3: Summary Alarm
#4: On Battery
<empty>
19200
<Not Installed>
Event #0
Call modem: no
ATZ0
None
None
Eaton Powerware logo
Disabled
Normal Sound
ABM cycling
Enabled
Enabled
2 strings for UPS-32 models
4 strings for UPS-64 models
34 W/cell
1.880 V/cell
S
164201553 Rev F www.powerware.com
OPERATION
59