Input Isolation Transformer Installation - Eaton Powerware 9155 User Manual

Double-conversion, split-phase, online uninterruptible 8–15 kva power system (ups)
Hide thumbs Also See for Powerware 9155:
Table of Contents

Advertisement

Chapter 5

Input Isolation Transformer Installation

The Powerware 9155 has the following power connections:
S
2-phase (L1 and L2), neutral, and ground connection for rectifier/bypass input
S
2-phase (L1 and L2), neutral, and ground connection for load output
S
The input isolation transformer output is always 240V (180° phase angle).
S
If installing a Maintenance Bypass Module (MBM) or Power Distribution Module (PDM), the UPS MUST
be set up for 240V output only; otherwise, the "Bypass Not Available" alarm annunciates. Any equipment
connected to the output requiring 208V (120° phase angle) is at risk for damage when using the
maintenance bypass switch.
S
The input isolation transformer cannot be used with a wall-mounted bypass switch.
Output overcurrent protection and disconnect switch must be provided by others.
Figure 12 and Figure 13 beginning on page 22 show the oneline diagrams of the input
isolation transformer with the UPS.
Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and
initial startup. Risk of electrical shock.
To hardwire the input isolation transformer and UPS (all hardware is supplied in the
accessory kit):
1.
Verify that the electrical connections to the installation site have been properly
installed.
2.
A wall-mounted, user-supplied, readily-accessible disconnection device must be
incorporated in the input wiring.
Compare the circuit breaker ratings and wire sizes to the specifications in Table 2
on page 19.
NOTE To accommodate the feature of easy system expandability, it is recommended that initial installation
of the Powerware 9155 UPS contain wiring to support the maximum capacity of the UPS cabinet.
3.
Switch off utility power to the distribution point where the UPS will be
connected. Be absolutely sure there is no power.
4.
Determine your equipment's grounding requirements according to your local
electrical code.
5.
Verify that the UPS battery circuit breaker is in the OFF position (see Figure 9).
6.
Verify that the input circuit breaker is in the OFF position.
7.
Remove the UPS wiring access cover and retain.
8.
Remove the input isolation transformer wiring cover and retain.
®
EATON Powerware
9155 UPS (8–15 kVA) User's Guide
C A U T I O N
W A R N I N G
S
164201553 Rev F www.powerware.com
17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents