Ups Terminal Block Wiring - Eaton Powerware 9155 User Manual

Double-conversion, split-phase, online uninterruptible 8–15 kva power system (ups)
Hide thumbs Also See for Powerware 9155:
Table of Contents

Advertisement

Table 1. UPS Terminal Block (TB1) Wiring
Wire Function
Terminal Position
Input
p
Ground
AUX
TB1-2-1 and 2-2
Not Used
TB1-2A-1 and 2A-2
L1
Neutral
L2
Output
p
L1
Neutral
L2
Not Used
TB1-8A-1 and 8A-2
Ground
* Use only 75°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16. Code may require a larger
AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements.
NOTE Input neutral must be wired for proper operation. Failure to connect an input neutral will void the
warranty.
Input Circuit Breaker
Rating
TB1-1
TB1-3
8 kVA
10 kVA
TB1-4
12 kVA
12 kVA
15 kVA
TB1-5
TB1-6
TB1-7
TB1-8
TB1-9
TB1
®
EATON Powerware
9155 UPS (8–15 kVA) User's Guide
Minimum Wire Size*
8 AWG
60A
4 AWG (21.2 mm
80A
3 AWG (26.7 mm
G (
100A
100A
2 AWG (33.6 mm
2 AWG (33.6 mm
100A
2 AWG (33.6 mm
8 AWG
8 AWG
8 AWG
8 AWG
1
3
4
5
2 2A
Input
Figure 7. UPS Terminal Block
S
164201553 Rev F www.powerware.com
UPS ONLY INSTALLATION
Tightening
Conduit Connection
Torque
25 lb in
25 lb in
2 access hole for
2" access hole for
(2.83 Nm)
1-1/2" conduit
2
)
2
2
)
)
2
2
)
)
2
)
25 lb in
2" access hole for
(2.83 Nm)
(2 83 Nm)
1-1/2" conduit
1-1/2" conduit
6
7
8
9
8A
Output
(Entry Size)
15