Eaton Powerware 9155 User Manual page 75

Double-conversion, split-phase, online uninterruptible 8–15 kva power system (ups)
Hide thumbs Also See for Powerware 9155:
Table of Contents

Advertisement

The UPS-mounted bypass switch has three positions as described in Table 10.
NOTE In the UPS or SERVICE position, AC input power is still connected to the input terminals inside the
UPS.
Table 10. UPS-Mounted Bypass Switch Positions
Switch Position
Description
UPS
Connects the UPS output to the load.
SERVICE
Connects the load directly to AC input power and disconnects UPS output. AC input
power is still connected to the UPS input.
BYPASS
Like the SERVICE position, BYPASS connects the load directly to AC input power and
disconnects UPS output. However, because BYPASS also disconnects AC input
from the UPS, this is the appropriate position for UPS maintenance or repair.
Figure 46 shows a UPS with a separate battery cabinet and a UPS-mounted bypass
switch.
Building
Service
Panel
UPS
Figure 46. Typical Hardwired Installation with UPS-Mounted Bypass Switch
®
EATON Powerware
9155 UPS (8–15 kVA) User's Guide
UPS-Mounted Bypass Switch
Bypass
Service
UPS
Bypass
Service
UPS
Bypass
Service
UPS
S
164201553 Rev F www.powerware.com
UPS MAINTENANCE
User-Supplied
Load
Distribution
Panel
EBM
69