Table 15. Technical Specifications
Technology
Online, double-conversion, split-phase topology with static bypass switch and
Input Voltage Range
Input Isolation
Transformer Input
Voltage Range
Input Power Factor
Input Rated Voltage
Input Frequency Range
Input Rated Frequency
Output Voltage
Regulation
Output Voltage
Distortion
Output Frequency
Output Frequency
Regulation
Output Frequency
Conversion
80%; Frequency Conversion mode can be configured through the front panel
Output Overload
Table 16. Model Specifications
Output Voltage (Line–Line)
Output Voltage (Line–Neutral)
Input Current*
Output Current
Output kVA (Line–Line Loads)
Output kVA (Line–Neutral Loads)
Output kW
Output Peak Current
Efficiency (Minimum)
Power Dissipation (BTU/hr)
DC Voltage (Supply)
* Input current for the input isolation transformer is 4% higher than for the UPS.
®
EATON Powerware
9155 UPS (8–15 kVA) User's Guide
optional 3-position maintenance bypass switch.
Frequency independent operation.
75–144 Vac per phase
208V or 240V ±20%
>0.99 at full load nominal line conditions
100/200, 110/220, or 120/240 Vac with 180° phase displacement
120/208 or 127/220 Vac with 120° phase displacement
50/60-Hz selectable, auto-configuring
±1% static, Phase to Neutral
±2% static, Phase to Phase
±5% dynamic at 100% resistive load change
Response time <1 ms
<2% THD linear load
<5% THD non-linear load
50/60-Hz selectable or auto-configuring
Synchronization to line
Frequency/phase-converter operation with derated output load capacity to
or through XCP commands.
Bypass is not available in Frequency Conversion mode.
101–110% for 10 minutes
111–125% for 60 seconds
126–149% for 5 seconds
>150% for 300 milliseconds
200
220
100
110
71A
71A
63A
63A
12.5
13.8
12.5
13.8
11.3
12.4
155
155
88%
88%
5582
5582
192
192
S
164201553 Rev F www.powerware.com
SPECIFICATIONS
45–65 Hz
15 kVA Model
240
208
120
120
71A
71A
63A
63A
15.0
13.0
15.0
15.0
13.5
13.5
155
155
88%
88%
5582
5582
192
192
220
127
67A
59A
13.0
15.0
13.5
155
88%
5582
192
75