Ups Maintenance; Ups And Battery Care; Storing The Ups And Batteries - Eaton Powerware 9155 User Manual

Double-conversion, split-phase, online uninterruptible 8–15 kva power system (ups)
Hide thumbs Also See for Powerware 9155:
Table of Contents

Advertisement

Chapter 12

UPS and Battery Care

Storing the UPS and Batteries

UPS Maintenance

This section explains how to:
S
Care for the UPS and batteries
S
Recycle used batteries or UPS
S
Use the maintenance bypass switch
For the best preventive maintenance, keep the area around the UPS clean and
dust-free. If the atmosphere is very dusty, clean the outside of the system with a
vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of 77°F (25°C).
NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of service life varies,
depending on the frequency of usage and ambient temperature. Batteries used beyond expected service
life will often have severely reduced runtimes. Replace batteries at least every 5 years to keep units
running at peak efficiency.
When storing the UPS and optional cabinets, the following requirements should
be met:
S
Verify that the battery circuit breaker is in the OFF position.
S
Avoid temperature and humidity extremes. To maximize battery life, the
recommended storage temperature is 59°F (15°C) to 77°F (25°C).
S
If you store the UPS for a long period, recharge the batteries every 10 months by
applying utility power. The batteries charge to 80% capacity in approximately
3 hours. However, it is recommended that the batteries charge for 48 hours after
long-term storage.
S
Check the battery recharge date on the shipping carton label. If the date has
expired and the batteries were never recharged, do not use the UPS. Contact your
service representative.
®
EATON Powerware
9155 UPS (8–15 kVA) User's Guide
S
164201553 Rev F www.powerware.com
67