17. Hardwire the input terminations (TB1-1 through TB1-3) for the input isolation
transformer.
See Table 2 for specifications and Figure 10 for a detailed view of the input
isolation transformer terminal block.
18. Punch a hole in the bottom of the MBM/PDM using a Greenlee punch or similar
device for wiring access.
Insert the supplied nylon bushing inside the wiring access hole.
19. Continue to the following chapter, "UPS-Mounted Bypass Switch Installation," to
complete the installation.
®
EATON Powerware
9155 UPS (8–15 kVA) User's Guide
INPUT ISOLATION TRANSFORMER INSTALLATION
S
164201553 Rev F www.powerware.com
21