11
Specifications
11.1
Specification Table
Model Number
INPUT
Rated Output Capacity
Rated Voltage
Nominal Input Current
Frequency
Topology
Primary Input Configuration
Optional Secondary Input
Input kVA
Power Factor
Walk-in Function
Inrush Current
Current Limit
Input THD Current
Battery (DC Link)
DC Nominal Voltage
Float Charge
Ripple Voltage
Charging Current
DC-AC Efficiency
OUTPUT
Rated Voltage
Rated Current
Rated Power Factor
Output Cables Required
Voltage Regulation (phase-
phase)
Voltage Adjustment Range
Phase Displacement
Rated Frequency
Frequency Regulation
Frequency Synchronization
Frequency Slew Rate
30
4300 Specifications
4310F3F300
30 kVA / 27 kW
208/120 VAC (+15% to -20%) (-20% to -30%)
82
50 ±5 Hz, 60 ±5 Hz (Can be used for frequency converter)
True On-Line double Conversion all-IGBT PWM with Active Input Power Factor
3 Phase; 4 Wire + GND
3 Phase; 4 Wire + GND
55 kVA (60 kVA Charging)
From 20% to 100% over 5 seconds
Less than 8X rated current under synchronous operation
83A
3 Phase; 4 Wire + GND
+/- 2% (0 – 100% balanced load)
+/- 3% (0 – 100% unbalanced load)
+/- 5 V from touchscreen
+/- 2º (0 – 100% balanced load)
+/- 4º (0 – 100% unbalanced load)
+/- 0.1% in free running mode
+/- 0.5/1.0/1.5/ Hz (+/- 1 Hz std.) Switch selectable by technician
1 Hz to 3 Hz (in 0.5 Hz steps)
4310F3F500
50 kVA / 45 kW
corrections
> 0.99 PF Lagging
115% Max current
< 3% @ 100% Load
288 V
324 VDC (+/- 2%)
0.5% rms
11.5 A
91.4%
208/120 V
139A
0.9 PF
50 / 60 Hz
4300 Series Installation and Operation Manual
4
138