Audible Alarm Functions - Toshiba 4300 series Installation And Operation Manual

4300 series three phase 30/50 kva ups
Table of Contents

Advertisement

13.6

Audible Alarm Functions

An audible alarm (buzzer) will sound when the UPS is in the battery backup mode, has a fault, has low
battery voltage, or is in an overload condition. The buzzer will also beep each time an effective item is
touched on the touchscreen. The following chart shows the buzzer pattern durations for each condition.
Time units are shown in seconds.
Condition
Any Fault (Intermittent buzz until fault clears)
Switch to Backup (Single five-second buzz)
Backup Operation (Intermittent buzz once every
ten seconds)
UPS Battery Shutdown Voltage
(Batt. Voltage 79% Normal)
Warnings:
OL110 (Overload Timer)
LB (Low Battery - Batt. Voltage 90% Normal)
BLFN (Battery Life Pre-alarm - Batt expires in 6
mo.)
BLFE (Battery Life End)
CHRGOV (Charger Over Voltage)
BTSTFL (Battery Test Fail)
BOH (Battery Overheat)
AOH (Ambient Overheat)
CLMT (Current Limit)
DCER (Display Disconnected)
BDEPL (Battery Depletion)
Touching Effective Item on Touchscreen
The buzzer can be silenced most easily by pressing the Buzzer Silent button on the Quack Access Toolbar.
Alternatively, the buzzer can also be silenced by selecting the Settings tab, then set the Buzzer Silent
parameter to Disable. This will turn off the buzzer for the current alarm status, but the buzzer will still sound
when the next Fault/Warning condition occurs.
The buzzer can be disabled permanently by selecting the Settings tab then setting the parameter Buzzer
Disable to Disable. This will disable the alarm so that no alarm sounds for any Fault or Warning condition.
66
TABLE 13.2 - AUDIBLE ALARMS
0.5 s
1.0 s
Audible Pattern
0.5 s
5.0 s
9.0 s
5.0 s
1.0 s
1.0 s
0.1 s
4300 Series Installation and Operation Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

4310f3f3004310f3f500

Table of Contents