12.16

Setup: Calibrating the Touchscreen

At anytime while using the tabs to view system details, the touchscreen can be calibrated by executing
the built-in calibration routine.
To calibrate the touchscreen:
1.
Press the Setup Tab.
2.
Press the DISP-EX 800 button
3.
Press the entry Cali to begin the calibration
routine
4.
Follow the directions on the display to
press the "+" at each location it flashes
on the display. To exit the calibration
routine press QUIT at any time.
See Fig. 2-10 A, B.
5.
After the touchscreen has been recalibrated
the display will indicate that the calibration
routine has passed. Press Quit to return
to the main display. See Fig. 2-10 C.
48
A
B
C
FIGURE 12-14 TOUCHSCREEN DISPLAY
CALIBRATION
4300 Series Installation and Operation Manual