Cisco MDS 9216 Hardware Installation Manual page 109

Hide thumbs Also See for MDS 9216:
Table of Contents

Advertisement

Appendix B
Technical Specifications
Send documentation comments to mdsfeedback-doc@cisco.com.
Table B-5
Power Requirements and Heat Dissipation for the 845 Watt Power Supply
Module Type /
Product Number
Cisco MDS 9216
chassis with fan module
DS-C9216-K9
Fixed supervisor
module (16-port FC
module, 1Gbps/2Gbps)
16-port FC module,
1Gbps/2Gbps
DS-X9016
32-port FC module,
1Gbps/2Gbps
DS-X9032
8-port IPS module
DS-X9308- SMIP
32-port ASM module,
DS-X9032-SMV
78-16165-01
Power
Heat
Required
Dissipation
(Watts)
(BTU/hr)
38
164 (.799)
220
940 (.799)
220
940 (.799)
200
855 (.798)
220
940 (.799)
295
1260
Table B-6
provides a sample calculation of power and heat dissipation for the
following hardware configuration at maximum wattage:
Cisco MDS 9216 chassis, including two 845 Watt AC power supplies
Fixed supervisor module, with 16 Fibre Channel ports
One 32-port Fibre Channel switching module.
Input Current
90 VAC
120 VAC
(amps)
(amps)
0.53
0.40
3.05
2.29
3.05
2.29
2.78
2.08
3.05
2.29
4.10
3.07
Cisco MDS 9216 Switch Hardware Installation Guide
Power Specifications
180 VAC
240 VAC
(amps)
(amps)
0.27
0.20
1.53
1.15
1.53
1.15
1.39
1.04
1.53
1.15
2.05
1.54
B-5