System Troubles - Gemini GEM-P801 Installation Instructions Manual

Control panel/communicator
Hide thumbs Also See for GEM-P801:
Table of Contents

Advertisement

System Troubles

Use the System Trouble chart on the following
page to determine the specific System
Trouble(s).
During normal panel operation the
TROUBLE LED has the following two modes of
operation:
1-7 possible trouble
STEADY
groups, AC is present
1-7 possible trouble
FLASHING
groups, AC is not present
Viewing System Trouble(s)
Press the
key on the keypad.
A4
To determine the System Trouble Group
Number, count the number of times the
SYSTEM TROUBLE LED blinks. The keypad
H
sounder will beep at the same rate that the
SYSTEM TROUBLE LED blinks.
H
To determine the System Trouble, note the zone
LED that is ON. Look up the specific system
trouble on the chart on the following page.
The
SYSTEM TROUBLE LED and keypad
H
sounder will continue to flash and beep. To view
the next System Trouble, if any, press the
key. Continue pressing the
E
no more system troubles to view, the system will
return to normal operation.
EXAMPLE
Enter
A4
and determine the specific trouble. Press any key to
view all system troubles.
SYSTEM
H
G E M I N I
H
Flashing
(System Trouble
Group Number)
Beeping
(System Trouble
Group Number)
Zone LED(s)
indicates
(Specific Trouble)
FIGURE
9 S
Note: System Troubles Groups 3 through 7 -
System Trouble Groups that have a zone or
smoke detector associated with the trouble,
such as RF low battery. The zone(s) of the
device with a low battery will be displayed by the
E
ZONE LED . For example, a wireless low
key, if there are
battery on zone 2 would beep the keypad
sounder 3 times and turn on zone 2 LED.
-
LOW BATTERY SYSTEM TROUBLE DISPLAY
to enter System Trouble mode
2
System Trouble
Group #
Keypad SYSTEM Trouble
LED
is
flashing
1
indicating System Trouble
Group 1.
Keypad Sounder beeps 1 time
indicating System Trouble
is ON
Specific Trouble
Zone 2 LED is ON indicating
Low Battery. (1 Beep, LED 2)
T
E
YSTEM
ROUBLE
XAMPLE
Audible System Trouble Indication - For all
system troubles, except when the only system
trouble is the loss of AC, the keypad will beep
once every 10 seconds. The keypad will continue
to beep until the reset button is pressed or the
trouble has been acknowledged by pressing the
key.
C
System Trouble Reporting
The following system troubles, when enabled to
report to Telco 1 [37-3] or Telco 3 [57-3], will send
the report code programmed in Trouble Report
[63] if reporting using a pulse format:
time
System Trouble
Pulse Report Code
Bell Cut
F1
2-Wire Fire Trouble
F1
Rcvr Fail-to-Respond
F1
Receiver Tamper
F1
Receiver JAM
F1
Tx Low Battery
F1
Tx Supervisory Failure
F1
Smoke Low Battery
F1
Smoke Sup. Failure
F1
If reporting using Point ID, a unique code will be
sent for each of the following System Troubles.
System Trouble
Point ID Report Codes
Bell Cut
CODE 1 321 G00 ZN000-BELL 1 TROUBLE
2-Wire Fire Trouble
CODE 1 373 G00 ZN000-FIRE LOOP TRBLE
Rcvr Fail-to-Respond
CODE 1 382 G00 ZN000-SENSOR TROUBLE
Receiver Tamper
CODE 1 145 G00 ZN000-EXP. MODL. TAMPER
Receiver JAM
CODE 1 333 G00 ZN000-FIRE LOOP TRBLE
Tx Low Battery
CODE 1 384 G00 ZN00n-RF TRAN LOW BATT
Tx Supervisory Failure
CODE 1 381 G00 ZN00n-SUPERVSN LOSS RF
A 300 (SYSTEM TROUBLE RST) code is sent if a restore is
reported after multiple troubles.
23