The requirements for Site Initiated Auto
Downloading are as follows:
1. Download Computer running PCPreset.
2. Program the telephone number of the
Download Computer in location [90]
Callback Telephone Number.
3. Program location [93] with the number of
the PCPreset account that is to be
downloaded.
PCPreset
1. Create the GEM-P801 account to be
downloaded
using
PCD-Windows
Quickloader Software.
1. Create a List using PCPreset.
2. Select the account by pressing
Select the desired account from the list of
PCD3000
accounts
available.
location in the list is the Auto Download
ID Number [93])
aD
3. Tag the list by entering
4. Enter Standby Mode by entering
The Computer is now in STANDBY
Site
At the site perform the following three steps:
1. Arm the panel.
2. Disarm the panel.
3. Enter
. The panel will now
A6
call the download computer running
PCPreset. PCPreset will answer the call,
establish
a
connection,
download the account that matches the
Auto Download ID Number [93] with the
account of the same number in the list
that PCPreset is currently running.

Dealer Programming

[94]Dealer Code
The default Dealer Code is
a new 4-digit Dealer Code. When the panel
is defaulted the Dealer Code will be
changed back to the default Dealer Code of
4567
only if Dealer Code Lockout [96-1]
has not been programmed.
[95]User 1 Code
The 1st User code is a program code as
t
.
well as an Arm/Disarm code. The default
User Code is
(The
Lockout is programmed the User 1 Code
cannot be programmed from User Program
Mode.
(
download)
[96]Dealer Options 1
o
.
(1) Dealer Code Lockout - Program to
prevent the Dealer Code from changing
with a panel default.
(2) User 1 Code Lockout - If programmed
the User 1 Code cannot be programmed
from User Program Mode.
(3) Household Fire - Activates the
following UL required features:
There is a 4 hour re-sound of wireless
Smoke Low Battery and wireless Smoke
and
then
Supervisory system troubles.
4567
. Program
1234
.
If User 1 Code
An active System Battery test performed
every 4 hours instead of 24 hours and
Wireless Smoke Supervisory Timer is set
to 4 hours.
Fire Bell Timing is March Time.
Wireless Smoke Supervisory Time is
fixed at 4 hours.
(4) Fire Trouble on Fire LED - Normally all
troubles are displayed on the
TROUBLE LED, including Fire Trouble. If
required Fire Trouble can be displayed on the
Fire LED.
Fire Trouble is indicated by a
steady IFire LED.
[97]Dealer Options 2
(1) International Dialing Protocol - No
dialing if no dial tone, 60 s between attempts
and 4 s wait for dial tone.
(2) Invert Bell Output - Inverts the Bell
polarity and removes supervision from the
bell circuit.
(3) System Trouble Auto Restore -
Normally,
System
troubles
acknowledgment (View System Trouble) in
order to restore. If this option is selected
troubles
will
restore
without
acknowledgment.
(4) User 1 Code-Program only - If enabled
User 1 Code will function only as the User
Program Code and will not Arm/Disarm the
panel.
SYSTEM
H
require
requiring
21