WI1089 GEM-P801 Installation Instructions

Installation

Mounting the Panel
Mount the Panel close to an unswitched AC
source, a cold-water pipe ground, and a
telephone line connection.
Mounting the Keypad
A keypad should be located near an exit/entry
door. To remove the keypad from the backplate,
insert a small screwdriver into the slots at the
bottom of the keypad. Pull up on the screwdriver
to pop off the cover.
Up to 4 keypads can be connected on individual
wire runs with #22 AWG wire with a maximum
total cable length of 1000 feet.
draws approximately 65 mA.
Keypad Wire Color
Control Panel Terminal
RED
12 (+PWR)
BLACK
13 (GND)
GREEN
14 (GREEN)
1 K
W
TABLE
EYPAD
IRING
Typical Fire Installation
(Where permitted by local codes)
Install smoke detectors outside each sleeping
area and on each floor, including the basement.
Install the living room and basement smoke
detectors near the stairway of the next upper
level.
For increased protection, additional
detectors should be installed in areas other than
6
those required, such as the dining room,
bedrooms and utility room.
rather than smoke detectors, are recommended
in kitchens, attics, and garages due to
conditions that may result in false alarms and
improper operation.
Refer to NFPA Standard 74 (National Fire
Protection Association, Batterymarch Park,
Quincy, MA 02269) for additional information,
including proper mounting methods.
Each keypad
3 Typical Fire Installation
FIGURE

Wiring

Heat detectors,
Grounding the Panel
Connect the control-panel EARTH GROUND
screw through a No. 16 AWG or larger wire to a
metal cold-water pipe. Do not use a gas pipe,
plastic pipe or AC ground connections. Use at
least #16 AWG wire.
ground lug crimped or soldered onto one end and
connect it to the EARTH GROUND screw in the
cabinet.
AC Power and Battery Wiring
Complete all wiring before connecting the battery
or AC Power. Do not plug the transformer into a
switched outlet.
Telephone Wiring
Wire as shown in the wiring diagram in the back
of this manual.
WARNING
The FCC restricts the use of this equipment on
certain telephone lines. Read the FCC statement
on the back of this manual to ensure compliance.
Connect a wire with a

Hide quick links: