Enter this command to turn the keypad sounder
ON/OFF. When the keypad is in Sleep mode all
keypad sounds will be silenced except for keypad
feedback beeps and Keypad Sounder on Alarm.
User Commands - Optional
Easy Exit
A 0
If enabled in Dealer programming, enter this
command while the panel is Armed to allow 3
minutes to exit the premises through Exit/Entry
and Exit/Entry Follower Zones.
Access on PGM
A 3
If enabled in Dealer programming, enter this
command to activate the PGM output (Terminal
15) for 5 seconds.

Dealer Commands

Download
(Programming Required)
A6
Establish a connection between the PCD-
Windows phone line and the Control Panel phone
line. When ready, tell the installer to arm, then
disarm. Then enter
A6
establish a connection. Phone connection to
installer will go "dead" as downloader and panel
connect.
Fault Find ON/OFF
A 7
Hardwired Zone Operation
Enter this command to turn Fault Find ON/OFF.
While in Fault Find mode, the loop response for
all zones will be set to the faster response of 40
ms. The keypad will beep for .25-seconds when
hardwired zones are faulted and for 1-second
when zones are restored.
Wireless Operation
Strength)
While in Fault Find mode the keypad will
provide an audible (Table 6) and visual (Figure
5)
indication of each transmitter's signal
strength. The signal strength metering is based
on a scale of 4 to 10, with 4 being marginal and
10 being excellent.
The keypad will beep out a number, from 1-4,
corresponding to the signal strength of the
transmitter. See Table 6.
second long. The keypad will sound a short
beep for transmitters with signal strengths of 3
or less.
SIGNAL STRENGTH
3 or less
4
in order to
5
6-7
8-10
TABLE
6
A
UDIBLE
(Signal
Each beep is 1-
KEYPAD SOUNDER
.25
S BEEP
BEEP
BEEP BEEP
BEEP BEEP BEEP
BEEP BEEP BEEP BEEP
S
S
I
IGNAL
TRENGTH
NDICATION
1
Signal Strength = 4
1 2
Signal Strength = 5
1 2 3
Signal Strength = 6-7
1 2 3 4
Signal Strength = 8-10
5 V
S
S
FIGURE
ISUAL
IGNAL
TRENGTH
Signal Strength Logging Mode
The Signal Strength Logging Mode is a
troubleshooting tool which allows the collection of
signal strength information for all transmitters on
the system. Normally the Signal Strength of
Supervisory Signals are not logged; during Signal
Strength Logging Mode the signal strength
information for all supervisory signals received
over a two hour period will be saved to the LOG.
Local Activation
Enable [92-4=ON], this will initiate a two hour test
period where all supervisory signals will log
signal strength information.
Remote Activation
Using PCD-Windows V4.1 Software, follow
the instructions below:
From the Status Screen:
Select [ Enable Signal Strength Logging ]
The Signal Strength logging mode will
automatically time out in 2 hours.