Gem-P801 Wiring Diagram - Gemini GEM-P801 Installation Instructions Manual

Control panel/communicator
Hide thumbs Also See for GEM-P801:
Table of Contents

Advertisement

E1
+
RED
RECHARGEABLE
BATTERY
12 VDC 4AH OR 7AH
E2
BLACK
RECOMMENDED BATTERIES YUASA
NP4-12 AND NP7-12
REPLACE EVERY FIVE YEARS
COLD WATER GROUND CONNECTION
USE ONLY COLD-WATER PIPE OR
BURIED GROUND ROD. USE AT LEAST
#16 AWG WIRE.
EARTH
GROUND
(1) COMBINED STANDBY = KEYPAD CURRENT + AUX POWER
CURRENT + FIRE POWER + PGM CURRENT.
(2) RESIDENTIAL FIRE REQUIRES A 7AH BATTERY.
(3) UNIT INTENDED TO BE MOUNTED VERTICALLY ON WALL.
(4) REFER TO WI1089 FOR COMPATIBLE TWO WIRE SMOKE
DETECTORS. DO NOT MIX DIFFERENT MODELS.
(5) THIS PANEL SHALL BE CHECKED BY A QUALIFIED
TECHNICIAN AT LEAST ONCE EVERY THREE YEARS.
(6) THIS PANEL SUPPORTS ONLY ONE SMOKE DETECTOR IN
ALARM.
(7) USE ONLY ONE BELL IN RESIDENTIAL FIRE APPLICATION.
(8) SYSTEM MUST BE TESTED AT LEAST ONCE A WEEK IN
THE AC/BATTERY MODE AND IN THE BATTERY-ONLY
MODE. (CONTACT CENTRAL STATION PRIOR TO
TESTING) AC MUST BE RESTORED AFTER TEST.

GEM-P801 WIRING DIAGRAM

(REFER TO INSTALLATION INSTRUCTIONS WI1089)
RESIDENTIAL BURG (4 HOUR STANDBY)
COMBINED STANDBY = 500 mA
RESIDENTIAL FIRE (24 HOUR STANDBY)
COMBINED STANDBY = 120 mA
1
2
+3
-4
+5
16 VAC 20 VA
TRANSFORMER
NAPCO TRF12
(OR EQUIVALENT
SEE WI1089).
Class 2 Transformer
DO NOT connect
to switched outlet.
2.2K
2.2K
ZONE 1 ZONE 2
ALL OUTPUTS ARE CURRENT LIMITED
4-Wire
Fire
Wiring
This equipment should be installed in accordance with Chapter 2 of the National Fire
Alarm Code, ANSI/NFPA 72-1996 (National Fire Protection Association
Batterymarch Park, Quincy MA 02269). and local codes. Information describing
proper installation, operation, testing, maintenance, evacuation planning, and repair
service is to be provided with this equipment. UL Listed Energy Cable is required.
BELL = 2.0 A
(2)
BELL = 95 mA
TEL LINE IN USE
+6
-7
+8
+9
-10 +11 +12 -13
2.2K
2.2K
2.2K
2.2K
ZONE 3 ZONE 4
ZONE 5 ZONE 6
FT2200
RED
Power
Power
Out (+)
In (+)
BLACK
Power
Power
Out (-)
In (-)
BROWN
Fire Loop
Fire
Out
Loop In
BROW
DS1
TELCO
JACK
14
15
16
17
FIRE
FIRE
BELL
GND
+PWR
GND GREEN
PWR
REMOTE BUS
+
+
+
GEM-RP8
+
+
GEM-RECV-XP8
2.2K
2.2K
2.2K EOLR
2.2K EOLR
(SUPERVISED)
GEM-P801 Terminals
12
Fire Power
10
Ground
12
Fire Power
13
Fire
DISCONNECT TELEPHONE
To RJ31X
(Supervised)
18
19
PGM
(-)
(+)
16
+PWR
WARNING
TO PREVENT RISK
OF ELECTRIC SHOCK
LINES PRIOR TO
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents