Format Of The Abb Spa Time String - Meinberg LANTIME/GPS Operating Instructions Manual

Etx 1he
Table of Contents

Advertisement

Format of the ABB SPA Time String

The ABB SPA Time String is a sequence of 32 ASCII characters starting with the
characters ">900WD" and ending with the <CR> (Carriage Return) character. The
format is:
The letters printed in italics are replaced by ASCII numbers whereas the other
characters are part of the time string. The groups of characters as defined below:
yy-mm-tt
_
hh.mm;ss.fff the current time:
cc
Check sum. EXCLUSIVE-OR result of the previous characters, displayed as a
HEX byte (2 ASCII characters 0..9 or A..F)
<CR>
Carriage Return (ASCII code 0Dh)
>900WD:yy-mm-tt_hh.mm;ss.fff:cc<CR>
the current date:
yy
year of the century
mm
month
dd
day of month
Space (ASCII code 20h)
hh
hours
mm
minutes
ss
seconds
fff
milliseconds
(00..99)
(01..12)
(01..31)
(00..23)
(00..59)
(00..59, or 60 while leap second)
(000..999)
129