PID fixed setpoint (PID-FF)

Number:
Parameter range:
Warnings
Faults
Function chart number:
Analog to the fixed frequencies (refer to Section 3.8), the PID controller has
separate programmable PID fixed setpoints. The values are defined using
parameters P2201 – P2207 and are selected using binector inputs P2220 – P2222.
The selected PID fixed setpoint is available via connector output r2224 where it can
be further processed (e.g. as PID main setpoint
3 methods are available to select the PID fixed setpoints, analog to the fixed
frequencies (Section 3.8):
Direct selection
Direct selection + ON command
Binary-coded selection + ON command
The methods are selected using parameters P2216 – P2218.
P0701 = 15
or
P0701 = 99, P2220 = 722.0, P2216 = 1
DIN1
Fig. 3-38
MICROMASTER 420
Operating Instructions
6SE6400-5AA00-0BP0
7
P2201 – r2224
-
-
FP3300, FP3310
P2220
r0722.0
Example to directly select the PID fixed frequency of fixed frequency 1 via
DIN1
P2253 = 2224).
1
0
2,3
0
P2201
. . . .
3 Functions
. . . .
r2224
109