Siemens MICROMASTER 420 Operating Instructions Manual page 163

0.12 kw - 11 kw
Hide thumbs Also See for MICROMASTER 420:
Table of Contents

Advertisement

Issue 07/04
Input voltage range
(with built in Class A Filter)
Order No.
6SE6420-
[kW]
Output Rating
[hp]
Output Power
[kVA]
Input Current 1)
[A]
Output Current
[A]
Fuse
[A]
Recommended
3NA
For UL specified
[mm
Input Cable, min.
[awg]
[mm
Input Cable, max.
[awg]
[mm
Output Cable, min.
[awg]
[mm
Output Cable, max.
[awg]
[kg]
Weight
[lbs]
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
supply V
of 400 V without line commutating reactor. If a line commutating reactor is used, the specified
values are reduced by between 70 % and 80 %.
* UL listed fuses such as Class NON from Bussmann are required for use in America
MICROMASTER 420
Operating Instructions
6SE6400-5AA00-0BP0
3 AC 380 V – 480 V, ± 10 %
2AD22-
2AD23-
2AD24-
2BA1
0BA1
0BA1
2.2
3.0
3.0
4.0
4.5
5.9
8.8
11.1
13.6
5.9
7.7
10.2
16
16
3805
3805
3807
*
*
2
]
1.0
1.0
17
17
2
]
6.0
6.0
9
9
2
]
1.0
1.0
17
17
2
]
6.0
6.0
9
9
3.1
3.3
6.8
7.3
= 1 % referred to the rated drive converter power and a rated line supply voltage
k
5 MICROMASTER 420 specifications
2AD25-
2AD27-
5CA1
5CA1
4.0
5.5
7.5
5.0
7.5
10.0
7.8
10.1
14.0
17.3
23.1
13.2
19.0
20
20
25
3807
3810
*
*
*
1.5
2.5
4.0
15
13
11
6.0
10.0
10.0
9
7
7
1.0
1.5
2.5
17
15
13
6.0
10.0
10.0
9
7
7
3.3
5.4
5.7
7.3
11.9
12.5
2AD31-
1CA1
11.0
15.0
19.8
33.8
26.0
35
3814
*
6.0
9
10.0
7
4.0
11
10.0
7
5.7
12.5
163