3 Functions
3.11.1

PID motorized potentiometer (PID-MOP)

Parameter range:
Warnings
Faults
Function chart number:
The PID controller has a PID motorized potentiometer which can be separately
adjusted. The functionality is identical with the motorized potentiometer (refer to
Section 3.9), whereby the PID parameters are emulated in the range from P2231 –
r2250 (refer to the comparison
Table 3-18
PID motorized potentiometer
P2231[3]
P2232
P2235[3]
P2236[3]
P2240[3]
r2250
108
P2231 – r2250
-
-
FP3400
Correspondence between the parameters
Setpoint memory of PID-MOP
Inhibit rev. direct. of PID-MOP
BI: Enable PID-MOP (UP-cmd)
BI: Enable PID-MOP (DOWN-cmd)
Setpoint of PID-MOP
CO: Output setpoint of PID-MOP
Table 3-18).
Motorized potentiometer
P1031[3]
Setpoint memory of the MOP
P1032
Inhibit reverse direction of MOP
P1035[3]
BI: Enable MOP (UP-command)
P1036[3]
BI: Enable MOP (DOWN-command)
P1040[3]
Setpoint of the MOP
r1050
CO: Act. output freq. of the MOP
MICROMASTER 420
Issue 07/04
Operating Instructions
6SE6400-5AA00-0BP0