3 Functions
The fixed frequencies can be selected via the digital inputs as well as also via
serial communication interfaces. The fixed frequency is selected, when using digital
inputs, using 2 techniques. This will be shown in the following example using the
fixed frequency P1001 and digital input 1 (refer to Fig. 3-32).
a) Standard methods
b) BICO methods
P0701 = 15 or P0701 = 99, P1020 = 722.0, P1016 = 1
P0702 = 15 or P0702 = 99, P1021 = 722.1, P1017 = 1
DIN1
DIN2
Fig. 3-32
Direct selection + ON command
When this fixed frequency is selected, the fixed frequencies are also directly
selected whereby the selection is combined with the ON command. When this
technique is used, a separate ON command is not required. The following is
obtained essentially analog to the example shown above:
a) Standard method
b) BICO method
100
P1020
r0722.0
0
P1021
r0722.1
0
Example for directly selecting FF1 via DIN1 and FF2 via DIN2
P0701 = 15
P0701 = 99, P1020 = 722.0, P1016 = 1
1
2,3
0
P1001
1
2,3
0
P1002
P0701 = 16
P0701 = 99, P1020 = 722.0, P1016 = 2
MICROMASTER 420
Issue 07/04
+
r1024
+
Operating Instructions